城市门站

城市门站

参考价: 面议

具体成交价以合同协议为准
2022-11-18 11:53:05
180
产品属性
关闭
河北欧意诺燃气设备有限公司

河北欧意诺燃气设备有限公司

免费会员
收藏

组合推荐相似产品

产品简介

概述该系列调压站通常采用撬装式结构.是天然气长输管线进入城市管网的关键设备.主要适用于天然气长输管线的分输线站、首站的下游或者城市的中压管网的上游作为城市门站

详细介绍


  概述该系列调压站通常采用撬装式结构.是天然气长输管线进入城市管网的关键 设备.主要适用于天然气长输管线的分输线站、首站的下游或者城市的中压管网的上游作为城市门站。燃气管网的配气站、CNG站等高-高、高-中压 燃气管网的调压和稳压:具有净化、计量、调压、分配。安全保护等功能.. 还可根据用户要求配置燃气报警系统.自控系统,加臭系统。也可以选装 RTU单元和通讯单元。
  OverviewThis series of pressure regulating stations is usually skid-mounted. Served as the key of supporting the gas long-distance transmission pipeline into the city pipe network, the equipment mainly applies to the branch station of the gas long-distance transmission pipeline as well as the downstream of the first station or the upstream of the city medium pressure network as the city gate station. The pressure regulation and stabilization of the high-high and high-medium pressure gas networks of the gas distribution station, CNG station, etc. of the gas networks have functions such as purification, metering, pressure regulation, distribution and safety protection. The equipment can also be configured with gas alarm system, automatic control system and odorization system according to the user’ s requirements, and can also be configured with optional RTU unit and communication unit.
  主要性能、参数:
  应用介质:各种燃气温度范围:-40℃~60℃允许进口压力:10MPa出口压力设定范围:0.1-4.0MPa压力调节:根据需要选用双路、三路或多路结构。
  响应时间:ta≤1s气体过滤:气液分离、过滤器气体加热:根播需要选用电加热或热水/蒸汽加热。
  压力调节:单路、双路、多路超压保护:监控、切断、放散气体计置:涡轮计量、孔板计量、超声波计量加臭系统:手动或自动阀门:球阀、碟阀{动作方式分为:手动、电动、气动}
  远稚控制:调压器出口压力,调节阀操作,切断阀操作,加臭数据采集:根据需要采集现场压力、温度、差压、流量、燃气组分、设备运行状态等通讯方式:RS232/RS485/无线电Main performance and parameters:
  Applicable medium: Various gasesTemperature range: -40℃~60℃Allowable maximum inlet pressure :10MPaOutlet pressure setting range:0.1-4.0MPaPressure regulation: Select a dual-path, three-path or multi-path structure as required.
  Response time: ta ≤ 1sGas filtration: Gas-liquid separation, filterGas heating: Select electric heatingor hot water/steam heating as required.
  Pressure regulation: Single-path, double-path or multi-pathOverpressure protection: Monitoring, cutoff or releaseGas metering: Turbine metering, orifice metering or ultrasonic meteringOdorization system: Manual or automaticValve: Ball valve or butterfly valve (the action mode includes: manual, electric and pneumatic)Remote control: Pressure regulator outlet pressure, control valve operation, cutoff valve operation and odorization data collection: Collect the field pressure, temperature, differential pressure, flow, gas component, equipment operation, etc. as required.
  Communication mode: RS232/RS485/radio